Tyco Sprinkler Tables
Compare Tyco sprinklers by product group, installation configuration, K-factor, connection and temperature rating.
Request a consultation
Swipe or scroll sideways to see all columns.
Standard Spray
| No, | Product image | Configuration | K-factor US (Metric) | Connection | Temperature ratings (°C) | Application | Sprinkler finishes | Escutcheon / cover finishes |
|---|---|---|---|---|---|---|---|---|
| 1 | ![]() | TY-FRB Upright / Pendent / Recessed Pendent SIN: TY1131; TY1231; TY2131; TY2231; TY3131; TY3231; TY4131; TY4231 | 2.8 (40.3); 4.2 (60.5); 5.6 (80.6); 8.0 (115.2) | ½″ NPT / ¾″ NPT | 57 / 68 / 79 / 93 / 141 | Light / Ordinary Hazard; K2.8: Light Hazard only Quick response; 3 mm bulb. See TFP171. | Natural Brass; Chrome Plated; White Polyester; Lead Coated | White Coated; Chrome Plated; Brass Plated Escutcheon styles 10 / 20 / 30 / 40. |
| 2 | ![]() | TY-FRB Horizontal / Recessed Horizontal / Vertical Sidewall SIN: TY3331; TY3431 | 5.6 (80.6) | ½″ NPT | 57 / 68 / 79 / 93 / 141 | Light / Ordinary Hazard Quick response; 3 mm bulb. See TFP176. | Natural Brass; Chrome Plated; White Polyester; Lead Coated | White Coated; Chrome Plated; Brass Plated Escutcheon styles 10 / 20. |
| 3 | ![]() | RFII (Royal Flush II) Concealed Pendent SIN: TY3551; TY3531 | 5.6 (80.6) | ½″ NPT | Sprinkler 68 → Cover 59; Sprinkler 93 → Cover 74 | Light / Ordinary Hazard Standard / quick response (5 / 3 mm bulb); ½″ vertical adjustment; optional dust and air seal. See TFP181. | Not separately stated | Chrome; Brushed Chrome; Brass; Signal White; Grey White; Custom |
Extended Coverage
| No, | Product image | Configuration | K-factor US (Metric) | Connection | Temperature ratings (°C) | Application | Sprinkler finishes | Escutcheon / cover finishes |
|---|---|---|---|---|---|---|---|---|
| 4 | ![]() | EC-5 Pendent / Recessed Pendent SIN: TY3232 | 5.6 (80.6) | ½″ NPT | 57; 68 | Light Hazard. Coverage up to 20 × 20 ft (6.1 × 6.1 m). See TFP228. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated Escutcheon styles 50. |
| 5 | ![]() | EC-5 Horizontal Sidewall / Recessed Horizontal Sidewall SIN: TY3302 | 5.6 (80.6) | ½″ NPT | 57; 68; 93 | Light Hazard. Coverage up to 16 × 24 ft (4.9 × 7.3 m). Commercial occupancies. See TFP298. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated Escutcheon styles 50. |
| 9 | ![]() | CHEC Concealed Horizontal Sidewall SIN: TY4332 | 8.0 (115.2) | ¾″ NPT | Sprinkler: 68 Cover plate: 59 | Light Hazard. Coverage up to 16 × 16 ft (4.9 × 4.9 m); concealed installation for architecturally sensitive areas. See TFP265. | — | Cover: Signal White; Pure White; Chrome Plated; Custom |
| 11 | ![]() | RFII (Royal Flush II) Concealed Pendent SIN: TY3532 | 5.6 (80.6) | ½″ NPT | Sprinkler / cover: 68 / 59 93 / 74 | Light Hazard. Maximum 20 × 20 ft (6.1 × 6.1 m), quick-response listing; flat cover plate. See TFP260. | — | Cover: Chrome Plated; Brass Plated; Signal White; Grey White; Custom |
Storage
| No, | Product image | Configuration | K-factor US (Metric) | Connection | Temperature ratings (°C) | Application | Sprinkler finishes |
|---|---|---|---|---|---|---|---|
| 1 | ![]() | ESFR-25 Pendent SIN: TY9226 | 25.2 (362.9) | 1″ NPT ISO 7-R1 | 74; 101 | ESFR suppression-mode protection of rack / high-piled storage. Catalog limits: storage up to 40 ft (12.2 m), ceiling up to 45 ft (13.7 m), subject to listing criteria. See TFP312. | Natural Brass |
| 5 | ![]() | ESFR-1 Pendent SIN: TY6226 | 14.0 (201.6) | ¾″ NPT | 74; 101 | ESFR suppression-mode rack storage protection. May eliminate in-rack sprinklers where permitted by the applicable listing. See TFP318. | Natural Brass |
| 7 | ![]() | ULTRA K-17 Upright — Specific Application Control Mode, 141°C | 16.8 (241.9) | ¾″ NPT | 141 | Control-mode storage sprinkler; 5 mm bulb. Catalog directs users to contact TYCO for technical details. | Natural Brass |
| 9 | ![]() | ELO-231 Pendent / Upright SIN: TY5111; TY5211; TY5811 | 11.2 (161.3) | ½″ NPT; ¾″ NPT | 74; 100; 141 | Extra large orifice; solder type. High-challenge storage protection at relatively low required pressures. Intermediate-level use with approved guard and shield. See TFP340. | Natural Brass; Chrome Plated; Lead Coated; Wax Coated; Wax over Lead Coated |
| 12 | ![]() | LD (Large Drop) Upright SIN: TY5153 | 11.2 (161.3) | ¾″ NPT | 68; 93; 141 | Control-mode protection of high-piled storage; 5 mm bulb. May eliminate in-rack sprinklers for qualifying applications. See TFP335. | Natural Brass |
| 14 | ![]() | TY-FRB Pendent / Upright — Intermediate Level SIN: TY3133; TY3231; TY4133; TY4231 | 5.6 (80.6); 8.0 (115.2) | ½″ NPT; ¾″ NPT | 57; 68; 79; 93; 141 | Intermediate-level sprinkler; 3 mm bulb. Factory-assembled integral water shield; for locations where sprinkler guards are not required. See TFP356. | Natural Brass; Lead Coated |
Dry Sprinklers
| No, | Product image | Configuration | K-factor US (Metric) | Connection | Temperature ratings (°C) | Application | Sprinkler finishes | Escutcheon / cover finishes |
|---|---|---|---|---|---|---|---|---|
| 2 | ![]() | DS-1 — 3 mm bulb Pendent / Upright / Horizontal Sidewall TY3235; TY3135; TY3335; TY3935; TY3735 | 5.6 (80.6) | ¾″ NPT/ 1″ NPT ; ISO 7-R1 | 57; 68; 79; 93; 141 | Light / Ordinary Hazard. For freezing exposure or seasonally drained systems; lengths up to 48″ (1220 mm). Seal prevents water entering the assembly until operation. See TFP510. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated |
| 3 | ![]() | DS-1 Extended Coverage Horizontal Sidewall TY3338; TY3358 | 5.6 (80.6) | 1″ NPT (standard order); ISO 7-R1 | 57; 68 | Extended coverage, Light Hazard. Coverage up to 16 × 20 ft (4.9 × 6.1 m) or 18 × 16 ft (5.5 × 4.9 m). Lengths up to 48″ (1220 mm). See TFP520. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated |
| 5 | ![]() | DS-1 Stainless Steel Horizontal Sidewall / Extended Coverage Horizontal Sidewall TY3337; TY3357; TY3339 | 5.6 (80.6) | 1″ NPT (standard order); ISO 7-R1 | 57; 68; 79; 93; 141; 182 | Quick- and standard-response options. Corrosive atmospheres; wet-pipe, dry-pipe or preaction installations. Extended coverage up to 16 × 20 ft (4.9 × 6.1 m). See TFP560. | Stainless Steel | Escutcheon: Stainless Steel |
| 7 | ![]() | DS-2 Extended Coverage Pendent TY5238 | 11.2 (161.3) | 1″ NPT (standard order); ISO 7-R1 | 57; 68; 79; 93; 141 | Extended coverage, Light / Ordinary Hazard; 3 mm bulb; extra large orifice. For freezing exposure or seasonally drained systems; lengths up to 48″ (1220 mm). See TFP540. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated |
| 8 | ![]() | DS-C Concealed Pendent TY3535; TY3555 | 5.6 (80.6) | 1″ NPT (standard order); ISO 7-R1 | Sprinkler / cover: 68 / 59 93 / 74 | Standard coverage. All hazards (standard response); Light / Ordinary Hazard (quick response). For freezing exposure or seasonally drained systems; lengths up to 48″ (1220 mm). See TFP515. | — | Cover: Chrome Plated; Brass Plated; White Painted; Custom |
| 10 | ![]() | DS-3 Extended Coverage Horizontal Sidewall TY5339 | 11.2 (161.3) | 1″ NPT (standard order); ISO 7-R1 | 68; 93 | Extended coverage, Ordinary Hazard; 3 mm bulb. Exterior loading docks and covered areas. For freezing exposure or seasonally drained systems; lengths up to 48″ (1220 mm). See TFP550. | Natural Brass; Chrome Plated; White Polyester | Escutcheon: White Coated; Chrome Plated; Brass Plated |
Special Purpose
| No, | Product image | Configuration | K-factor US (Metric) | Connection | Temperature ratings (°C) | Application | Sprinkler finishes | Escutcheon / cover finishes |
|---|---|---|---|---|---|---|---|---|
| 1 | ![]() | ATTIC BB (Back-to-Back) / HIP / SD (Single Directional) / AP (Attic Plus) SINs: TY4180; TY4181; TY4182; TY3180; TY3181; TY3182; TY2180; TY2181; TY2182; TY3183; TY3184; TY3185; TY3187; TY3190; TY2190 | 4.2 (60.5); 5.6 (80.6); 8.0 (115.2) | ½″ NPT; ¾″ NPT | 93; 100 | Specific-application attic protection; wet- or dry-pipe systems. Catalog describes attic widths up to 60 ft (18.3 m) using a single pipe line. Specifications are grouped by family; verify model-specific selection in TFP610. | Natural Brass | — |
| 2 | ![]() | CC1 — TY1189 Combustible Concealed Space, Upright | 2.8 (40.3) | ½″ NPT | 79 | Specific-application protection of qualifying Light Hazard combustible and noncombustible concealed spaces. Listed BlazeMaster CPVC applications in combustible concealed areas; see TFP630. | Natural Brass | — |
| 3 | ![]() | WS — TY3388; TY3488 Window Sprinkler, Horizontal / Pendent Vertical Sidewall | 5.6 (80.6) | ½″ NPT | 68; 93 | Specific-application glazing protection. Catalog describes assemblies with ratings up to 2 hours; rating depends on the listed glazing assembly and installation criteria. See TFP620. | White Polyester Coated; Chrome Plated; Natural Brass | — |
| 4 | ![]() | RAVEN Institutional Pendent / Horizontal Sidewall TY3281; TY3282; TY3381; TY3382 | 5.6 (80.6) | ½″ NPT | 74 | Quick response; standard or extended coverage variants. Tamper-resistant design for correctional, detention, mental health care and other commercial facilities. Catalog pressure: 175 psi (12.1 bar). See TFP651. | Chrome; White | Escutcheon: Chrome; White |
| 5 | ![]() | Issue D QUARTZOID High Temperature, Upright / Pendent TY3191; TY3296; TY4191; TY4292 | 5.6 (80.6); 8.0 (115.2) | ½″ NPT; ¾″ NPT | 204; 260; 343 | Standard coverage; all hazards. Extra-high and ultra-high temperature ratings; 11 mm bulb. Corrosion-resistant coating options. See TFP690. | Natural Brass; Chrome Plated; Lead Coated | — |
| 6 | ![]() | TY-B / TY-FRB — Alternate Materials Vertical Sidewall / Horizontal Sidewall / Recessed Horizontal Sidewall | 5.6 (80.6) | ½″ NPT | 57; 68; 79; 93; 141; 182 | Corrosion-resistant standard coverage spray sprinklers for commercial occupancies. TY-B: standard response, 5 mm bulb. TY-FRB: quick response, 3 mm bulb. Verify variant-specific temperatures and SINs in TFP680. | Materials: Stainless Steel; SMO (stainless-molybdenum alloyed); Titanium | Finish not stated in catalog; escutcheon style 10 |